Drinking Water Quality Standards
1.中華民國八十七年二月四日行政院環境保護署(87)環署毒字第 00044 28 號令訂定發布全文 9 條;除另定施行日期者外,自發布日施行 2.中華民國九十二年五月七日行政院環境保護署環署毒字第 0920028896 號令修正發布第 3 條條文 3.中華民國九十四年五月三十日行政院環境保護署環署毒字第 094003989 4E 號令修正發布第 3~5 條條文;並刪除第 6 條條文 4.中華民國九十七年一月二日行政院環境保護署環署毒字第 0960100652 號令修正發布第 3 條條文;除另定施行日期者外,自發布日施行 5.中華民國九十八年十一月二十六日行政院環境保護署環署毒字第 09801 06331E 號令修正發布第 3 條條文 6.中華民國一百零三年一月九日行政院環境保護署環署毒字第 103000122 9 號令修正發布第 3 條條文 7.中華民國一百零六年一月十日行政院環境保護署環署毒字第 106000088 1 號令修正發布第 3~5 條條文 8.中華民國一百十一年五月二十三日行政院環境保護署環署水字第 11110 59186A 號令修正發布第 5 條條文;增訂第 5-1 條條文 中華民國一百十二年八月十八日行政院院臺規字第 1121028221 號公告 第 2 條、第 7 條、第 8 條所列屬「行政院環境保護署」之權責事 項,自一百十二年八月二十二日起改由「環境部」管轄 9.中華民國一百十三年十一月二十五日環境部環部水字第 1131072826 號 令增訂發布第 3-1 條條文;除第 3-1 條第 1 項自一百十六年七月 一日施行外,自發布日施行
資料來源:全國法規資料庫(ChOrder.json,版本 2026/7/24 上午 12:00:00)・政府資料開放授權
These Standards are determined pursuant to Article 11, Paragraph 2 of the Drinking Water Management Act (herein referred to as "this Act").
These standards shall apply to drinking water supplied from drinking water equipment designated in Article 4 of this Act and other drinking water designated by the central competent authority.
1Regulations of these standards are set forth herein.
2I. Bacterial standards: (Samples for total bacterial count must be collected from the finished water distribution networks that receive water from water treatment utilities with disinfection regime)
3II. Physical standards:
4III. Chemical standards:
5A. Substances that impact health:
6B. Substances with potential health impact:
7C. Contaminants that cause aesthetic, cosmetic, and technical effects:
8D. Limit range of residual chlorine (Limited to water supply systems using chlorine as disinfectant):
9E. Range for pH index (water treated by stationary continuous water supply equipment on public or private premises are not be subjected to this limitation):
1The standards for Per- and Polyfluoroalkyl Substances (PFAS) are as follows:
2The water supply entities or management entities of water purification equipment shall, from January 1, 2025, until the effective date mentioned in the preceding paragraph, conduct water quality testing as follows: for equipment with a water supply exceeding 20,000 cubic meters per day, testing shall be performed at least twice, with a minimum interval of 360 days between tests. For equipment with daily water supply below 20,000 cubic meters, at least one test shall be conducted. If any water quality parameter exceeds the maximum limit, the water supply or management entities of the water purification equipment must, within seven days of the issuance of the test report, notify the central competent authority, the central competent authority under the Water Supply Act, and the competent authority of the municipality or county (city) where the equipment is located. Additionally, within 30 days, they must submit a drinking water quality management plan to the central competent authority for record-keeping and send a copy to the central competent authority under the Water Supply Act and the competent authority of the municipality or county (city) where the equipment is located.
3If, before the effective date mentioned in the preceding paragraph, the competent authority conducts random water quality inspections and finds that the drinking water quality test values exceed the maximum limit, the competent authority shall notify the water supply or management entities of the water purification equipment to make improvements. The water supply or management entities must, within 30 days after receiving the notification, submit a drinking water quality management plan to the central competent authority for record-keeping and send a copy to the central competent authority under the Water Supply Act and the competent authority of the municipality or county (city) where the equipment is located.
4
1For tap water, simple water supply and treatment facilities, and community-installed public water supply systems, when source water turbidity value exceeds 1,500 NTU caused by torrential rains or other natural disasters, the maximum turbidity limit for drinking water may apply to 4 NTU.
2Drinking water source turbidity testing data in the foregoing paragraph shall be provided by tap water enterprises, simple water supply and treatment units or community-installed public water supply units.
For tap water, simple water supply and treatment facilities, and community-installed public water supply systems, when source water turbidity value exceeds 1,500 NTU caused by torrential rains or other natural disasters, the limit range of free residual chlorine may apply to the following values (shall apply only to water supply systems that add chlorine disinfectants).
1For tap water that needs to be supplied by zones due to the natural disasters described in the preceding article, during the natural disaster response actions period, the drinking water quality standards in the supply districts are as follows.
2I. Limit range of free residual chlorine (shall apply only to water supply systems that add chlorine disinfectants).
3II. Physical standards:
4III. Contaminants that cause aesthetic, cosmetic, and technical effects:
5The natural disaster response actions period described in the first paragraph referred to the period which Central Emergency Operation Center is established to deal with natural disasters, in accordance with Article 13, Paragraph 1 of the Disaster Prevention and Protection Act.
(Deleted)
Testing methods for each water quality item designated in these Standards shall be designated and officially announced by the central competent authority.
A competent authority that conducts water quality analysis in accordance with these Standards may commission an approved analysis laboratory to assist with analysis.
Unless an implementation date is separately designated, the regulation items in these standards shall take effect on the date of promulgation.
5The implementation deadlines for the previous three drinking water quality management plans shall not exceed the effective date specified in paragraph 1.